
Links:
An important point to note is that Liquid floodback is one of the leading causes of compressor failure. Liquid floodback is determined as "Liquid refrigerant returning to the compressor when it is running".
A large proportion of the compressors we recondition are the result of liquid floodback and liquid slugging,the compressors are reconditioned back to new, however if the problem which caused your initial compressor failure still exists, you will experience compressor failure again.
These sites provide some useful information on the web in diagnosing your system problems and making sure they are fixed.
http://www.hvacfun.com/a-once-prevent-years-service-comps.htm
http://www.fridgetech.com/articles/recipfailmodes/
http://www.progresssupply.com/source/february2001.pdf
http://www.ultimatehvac.com/LinkedDocs/COMPRESSORFAILURES.pdf
http://www.danfoss.com/NR/rdonlyres/CA85447B-C096-459F-B861-3BFD680DBC28/0/FSN008web.pdf
http://www.hvactechsupport.com/ac-component-analysis.asp
Often a service contractor may see a compressor that failed due
to floodback, but because of the severity of the damage, he may misdiagnose
the problem. System-based causes of slugging and floodback may be different
from each other; finding the root of the problem is essential
to prevent it from happening again.
There can be multiple system causes of floodback, even as basic as lack of airflow
because the system’s filter has not been changed. It also may be a problem
with the expansion valve, but then again, it may not be. A contractor or service
technician should never jump to this conclusion. The metering device may lose
control, but this does not mean that the root of the liquid floodback was a
metering device problem. For instance, if the evaporator coil freezes over,
if an evaporator fan fails, the liquid will not be properly evaporated. This
liquid then returns to the compressor, and the result is severe damage or failure
due to floodback.
Depending on the style of compressor, an observant contractor or service technician will see different failure patterns. These are observable by sending it to Ganley's and requesting them to perform a teardown and report, which is performed for a minimal fee. This can put you in the right direction of determining the cause.By determining the failure patterns within the compressor, a service contractor can do a better job of determining what types of system problems may have led to the compressor’s damage.
A refrigerant-cooled compressor, for example, is one that requires the return gas to flow across the motor before entering the compressor, in order to keep the motor from overheating. In this type of floodback situation, the liquid refrigerant would mix with the oil in the crankcase and would result primarily as low-end wear, such as worn bearings and worn rods.
An air-cooled compressor is one where the return gas does not flow across the motor; instead, it enters into the side of the compressor, very near the compression chamber. In a floodback situation, the liquid would enter the compression chamber and would be more likely to result in a liquid slug (compression of liquid in the cylinder area).
Can you have floodback in a welded compressor? It’s possible, even though many safeguards will protect the compressor from system-related damage. If floodback were to occur due to long-term operating conditions, keep in mind that all welded compressors are refrigerant-cooled; therefore, contractors and service technicians should look for damage in the running gear, bearings, rods, and crankshaft areas:
Liquid refrigerant displaces oil as it travels through the crankshaft. Also,
liquid refrigerant is a solvent and washes the oil film from adjoining surfaces;
this, in turn, causes wear. Scoring will be evident.
While the compressor is operating, the technician should check superheat at
the compressor. If floodback has been a problem, a minimum of 20 degrees F superheat
would be desirable.
While the results of liquid floodback can include severe damage and premature
failure of the compressor, it is also highly preventable.
Proper routine maintenance and regular inspections (including measurement of
superheat and subcooling, where appropriate) go a long way toward preventing
liquid floodback conditions, and ensuring long life for the compressor.
Other useful links ;
Ganley Refrigeration Services Ltd Warranty conditions:
http://www.hvacindia.org.in/journals/2000apr/article04.html
http://www.bristolcompressors.com/InfoDocs/ap-135.pdf
